XT-40 Models


Product Name:XT-40 Models
Product Model:XT40 3Y201,XT40 1P201
Updated:2010.04.13
Views:2

X T 4 0 R A N G E

XT40 models provide cost effective surge suppression for your electrical and electronic equipment. UL1449 listed circuitry intercepts potentially damaging transients at small service entrance or sub-distribution panel locations before they can affect valuable equipment. Compact size provides application flexibility and close proximity mounting to minimise parallel connection lead lengths for optimum product performance.

GENERAL SPECIFICATIONS:

DESCRIPTION: Parallel configured, hard wire connected Transient Voltage Surge Suppressor providing 40kA per phase peak surge current.
APPLICATION: Location categories B and A, medium and low exposure level, AC power distribution boards,final circuit distribution boards and individual equipment isolators.
WARRANTY: 10-Year Free Replacement warranty.
UNIT LISTINGS: UL1449 Second Edition.
QUALITY: ISO 9001: 1994 Quality System Certification BSI FM 30833.

MECHANICAL SPECIFICATIONS:

ENCLOSURE: IP66 rated aluminium weatherproof enclosure.
MOUNTING: Factory installed internally threaded conduit fitting and multi-point mounting holes. Flush mounting plate available, order list number ZPLATE-2.
CONNECTION: Standard products include approx. 450mm factory fitted stranded cable #10 AWG (≈ 6mm2).
SHIPPING WEIGHT: 1.3kg.

ELECTRICAL AND PERFORMANCE SPECIFICATIONS:

CIRCUIT DESIGN: Bi-directional, parallel configured, Threshold Response circuitry utilising advanced component encapsulation technology.
PROTECTION MODES: All Mode: line to neutral & line to line (normal mode) and line to earth & neutral to earth (common mode).
SUPPLY FREQUENCY: 50-420Hz.
RESPONSE TIME: ≤ 1 nanosecond.
EMI/RFI ATTENUATION: Up to 41dB normal mode, up to 40dB common mode.
CAPACITANCE: 2.3μF.
CIRCUIT DIAGNOSTICS: 1 LED indicator per phase, normally on.

TEST PERFORMANCE DATA:

LIST NUMBER SYSTEM
CONFIGURATION
NOMINAL SYSTEM
VOLTAGE(rms)
ANSI/IEEE C62.41 - 1991 MEASURED LIMITING VOLTAGE TESTS*
A3 RING WAVE
2,000V 200A
90° PHASE ANGLE
B3/C1 IMPULSE
WAVE, 6,000V 3,000A
90° PHASE ANGLE
C3 IMPULSE
WAVE, 20,000V 10,000A
90° PHASE ANGLE
XT40 1P201 SP N & E 200, 208, 220
230, 240
L-N <500V L-N <600V L-N <1500V
XT40 3Y201 TP N & E
STAR CONNECTED
220/380 230/400
240/415 277/480
L-N <500V L-N <600V L-N <1500V